Part Number: ETM4039 | Manufacturer: Spd Electrical Systems Inc | NSN: 5925-00-783-6221 (5925007836221) | Item Name : circuit breaker | CAGE Code: 30086 | FSC: 5925 Circuit Breakers |
The ETM4039 with NSN 5925007836221 is available in stock! Thanks for your interest in AerospaceSimplified.com. ETM4039, Circuit Breaker part is manufactured by Spd Electrical Systems Inc. Want to request a quote for it? Please fill the form below with contact details, expected delivery date, and quantity.
AerospaceSimplified.com is owned and operated by ASAP Semiconductor – a leading distributor of Spd Electrical Systems Inc NSN parts in US. We stock ready-to-ship NSN parts from over 5000 manufacturers. We have headquarters in California, We can ship products the same day. A dedicated sales executive will contact you within 15 minutes of receiving the RFQ for ETM4039 part. For even faster service you can call us at +1-714-705-4780. For multiple part number, you can email us your Bill of Materials (BOM) at sales@aerospacesimplified.com
For safe and secure sourcing on the go, download the ASAP Semiconductor app on Google Play or the Apple App Store.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-783-6221 Item Description: Circuit Breaker | 5925 | 007836221 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | 0 | ||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Etm4039 | 2 | 2 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 90.0 AMPERES AC ALL LOCATIONS AND 90.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 47.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 110.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 14.000 MINIMUM AT 300 PCT ALL LOCATIONS AND 29.000 MAXIMUM AT 300 PCT ALL LOCATIONS |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 SCREW |
ADTV | CASE MATERIAL | PLASTIC |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |